Parameter
General
(cont.)
9C LON subscriber monitoring
Display
No monitoring
20 min
... min
Boiler
Parameter values in bold are factory settings.
02 Burner type
!
Display
Single stage burner
Two-stage burner
Modulating burner
03 Boiler protection, gas/oil operation
Display
Gas operation
Oil operation
Resetting to gas not possible.
04 Switching hysteresis burner
Display
Switching hysteresis 4 K
ERB50 function
ERB80 function
68
Value
Explanations
Displayed only if parameter "76:1" has been set.
Note
To prevent fault messages, we recommend settings
greater than 5 minutes.
9C:0
9C:20
LON subscriber monitoring
If there is no response from a subscriber for 20 min,
the values specified in the control unit are used. Only
then will a fault message be issued.
9C:1 to
9C:60
Value
Explanations
02:0
02:1
02:2
!
Value
Explanations
03:0
03:1
Value
Explanations
Note
Factory setting, according to coding card
■
Only for single stage burner
■
04:0
04:1
04:2