Set Flow Temperature For Cylinder Heating - Viessmann Vitotronic 11 CC1E Installation And Service Instructions Manual

Table of Contents

Advertisement

Domestic hot water

05 Set flow temperature for cylinder heating

Display
Set system flow temperature
Max. set system flow temperature for DHW
heating
06 Differential, set boiler water temperature to set DHW temperature
Display
20 K if the set boiler water temperature is
above the set cylinder temperature
... K if the set boiler water temperature is
above the set cylinder temperature
07 Circulation pump for cylinder heating
Display
The circulation pump for tank heating starts
depending on the boiler water temperature
Started immediately.
08 Circulation pump run-on
Display
10 min
No run-on
... min
09 Frequency, auxiliary function for DHW heating
Display
Without
Daily
Every 2 to 14 days
2 x daily
(cont.)
Value
05:0
05:1
Value
06:20
06:0 to
06:50
Value
07:0
07:1
Value
08:10
08:0
08:1 to
08:15
Value
09:0
09:1
09:2 to
09:14
09:15
Explanations
The set flow temperature is determined by the highest
system flow temperature demand.
The set flow temperature is determined by the cylinder
flow temperature demand.
Explanations
During DHW heating, the boiler water temperature is
at least 20 K higher than the set DHW temperature.
Differential between the boiler water temperature and
the set DHW temperature
Adjustable from 0 to 50 K
Explanations
Not effective if parameter "00:3" has been set.
Explanations
Circulation pump with max 10 min run-on time after
cylinder heating
No circulation pump run-on
Explanations
Parameter
75