5
Electrical installation

Controller mains connection for a mains voltage of 400 V

5.2
Controller mains connection for a mains voltage of 400 V
(
Stop!
The user is responsible for sufficient strain relief!
L1
L2
M8
L1, L2,
25-30 Nm
L3
221-264 lb-in
Fig. 5−2
Fuses and cable cross−sections for the mains supply
Type
EVF9335−EV
EVF9335−EVV030
EVF9335−EVV060
EVF9335−EVV110
EVF9336−EV
EVF9336−EVV030
EVF9336−EVV060
EVF9336−EVV110
EVF9337−EV
EVF9337−EVV030
EVF9337−EVV060
EVF9337−EVV110
EVF9338−EV
EVF9338−EVV030
EVF9338−EVV060
EVF9338−EVV110
82
L3 PE
BR1
BR2
40 mm
M6
PE
15-20 Nm
133-176 lb-in
Mains connection example
BR1, BR2
Brake resistors can only be operated with variants V060 and V110
For connection see the 9300 vector System Manual
Fuse
250 A
315A
315A
400 A
1)
Multiple conductor; both conductors must have the same cross−section
2)
Lenze recommends to use fuses of the gRL utilisation category
Observe the national and regional legislation
l
PE U
V
W
Installation to EN 60204−1
2)
L1, L2, L3 [mm
150
2 × 50
150
2 × 50
150
2 × 50
240
2 × 95
9300VEC003
2
2
]
PE [mm
]
95
1)
95
1)
95
1)
150
1)
EDKVF9338 DE/EN/FR 4.0