Basic unit wiring
Basic units in the power range 0.25 ... 2.2 kW

Power connections for 400 V mains voltage

6.4.3
Power connections for 400 V mains voltage
Mains connection 400/500 V
8200 vector 0.55 ... 2.2 kW
L
( ( ( (
Stop!
Controller type E82EVxxxK 4 C must only be connected to a
l
mains voltage of 3/PE AC 320 ... 500 V. Higher mains voltages
will destroy the controller!
The discharge current to PE is > 3.5 mA. EN 50178 requires a
l
fixed installation. Double PE connection required.
E82EV551K4B
E82EV751K4B
E82EV152K4B
E82EV222K4B
X1.1
L1
+UG -UG
L2/N
L1 L2
3/PE AC 400 V
Fig. 6.4-3
Mains connection 400/500 V 0.55 ... 2.2 kW
X1.1/+UG,
DC supply (DC-bus operation - see Operating Instructions)
X1.1/-UG
EDS82EV903-1.0-11/2002
L3 PE
L3
PE
6
6.4
6.4.3
X1.1
8200vec011
6.4-5