Connection plan for controllers type E82xVxxxK4C (400/500 V mains)

Connection plan for controllers type E82xVxxxK4C (400/500 V mains)
(
Stop!
Only connect the controller to the permitted mains voltage (^ Technical data). A
ƒ
higher mains voltage destroys the controller!
Some controllers may only be actuated with a mains choke or mains filter. This
ƒ
requirement can differ with regard to operation at rated power and operation at an
increased rated power.
The leakage current to earth (PE) is > 3.5 mA. In accordance with EN 61800−5−1 a
ƒ
fixed installation is required. The PE conductor has to be designed double.
E82EV551K4C
E82EV751K4C
E82EV152K4C
E82EV222K4C
L1
+UG -UG
X1.1
L1 L2
3/PE AC 400 V
X1.1/+UG, X1.1/−UG
Supply for DC−bus operation
EDK82EV222 DE/EN/FR 13.0
L2
L3 PE
L3
PE
Electrical installation
X1.1
l
Mains connection