Maintenance

9.1

Replacing modules

Replacing modules
Replacing a module is not permitted during ongoing operation.
Material damage can occur
If you remove/insert modules with the power connected, this can lead to undefined states in
your system.
Material damage to the ET 200AL distributed I/O system may occur as a result.
Only remove or replace modules when the power is disconnected.
Always comply with the required standards and safety guidelines when configuring a
system.
Mixing up ET-Connection1 and ET-Connection2
When connecting the modules, always ensure that they are properly connected.
If you mix up the lines for ET-Connection1 and ET-Connection2 when connecting the
modules, this can lead to undefined states in your system.
Behavior of ET-Connection
During ongoing operation, a module replacement may be necessary, e.g. because the
module is defective. If an I/O module fails in an ET-Connection line, the line remains active
up to the failed I/O module. After replacing the I/O module, the ET-Connection line starts up
by itself.
Procedure
To replace a module, proceed as follows:
1. Disconnect the supply voltage to the module to be replaced.
2. Completely remove all cables connected to the module.
3. Completely remove the fixing screws of the module
76
WARNING
WARNING
Distributed I/O system
System Manual, 08/2019, A5E31861578-AG
9