Accessories/spare parts
C.2 Cables
The following table shows the technical properties of the connecting cable for
ET-Connection, PUR cable.
Table C- 11
General information
Product type designation
Function
Degree of protection and protection class
IP65
IP67
Ambient conditions
Ambient temperature during mounting
minimum
maximum
Storage/transport temperature
Ambient temperature during transport and storage
minimum
maximum
Cables
Cable designation
Number of electrical wires
Design of shielding
Cable length
Outside diameter of the inner conductor
Outside diameter of the wire insulation
Outside diameter of the cable sheath
Permissible bending radius
One time bending, min.
Multiple bending, min.
Constant bending
Color of the cable sheath
Color of the wire insulation of the data wires
Weight per length
Mechanics/material
Type of cable outlet
Connector housing material
Wire insulation material
Cable sheath material
Material property halogen free
Material property silicon free
104
Connecting cables for ET-Connection, PUR cable
CONNECTING CABLE FOR BUS CABLE ET-
CONNECTION, PUR CABLE 0.2 M
To connect two bus cables ET-CONNECTION
Yes
Yes
-30 °C
80 °C
-40 °C
80 °C
2Y(ST)C11Y 2x2x0.5/1.0-100-GN
4
Overlapped aluminum-lined sheet, coated with
shielding made of tin plated copper wires
0.2 m
0.5 mm
1.0 mm
5 mm
20 mm
40 mm
100 mm
Green
White, yellow, blue, orange
34 kg/km
180° cable outlet
Metal
PE
PUR
Yes
Yes