PROFINET IO
4.2 Interrupts/diagnostics alarms
Diagnostics alarm
Error code
Wire break
6
H
Error
9
H
Load voltage 2L+
11
missing
Short-circuit to ground 106
4.2.3.2

Maintenance events

Triggering of a maintenance event
The MultiFieldbus interfaces of the ET 200eco PN M12-L support the diagnostics concept and
maintenance concept in PROFINET according to the IEC 61158-6-10 standard. The goal is to
detect and remove potential problems as soon as possible.
The I/O device signals a maintenance event to the higher-level diagnostic system on the
following event:
Table 4-8  Triggering of a maintenance event
Maintenance alarm
Maintenance demanded
MT/IO LED is lit
System alarms in STEP 7
The maintenance information is generated in STEP 7 with the following system alarms:
• Maintenance demanded - indicated for each port by a yellow wrench icon
view or in the hardware configuration.
You can find additional information in the STEP 7 online help.
32
Meaning
Channel not connected (open)
Internal module error has occurred
Load voltage 2L missing or too low.
H
Short-circuit to ground
H
Error code
2
H
I/O device digital outputs DQ 8x24VDC/0.5A M12-L 8xM12 (6ES7142-6BG00-0BB0)
Corrective measures
Replace the I/O device.
Check the supply voltage on the I/O device.
Event
Meaning
Undervoltage
Supply voltage 1L+ is below the tolerance limit.
Equipment Manual, 03/2023, A5E46570894-AD
Disable diagnostics
Connect a resistor to the actuator con­
tacts in the load resistance range.
Correct the process wiring.
Replace the defective actuator.
in the device