Fuse And Reactor Specieications - LSIS LSLV-S100 Series Operation Manual

Hide thumbs Also See for LSLV-S100 Series:
Table of Contents

Advertisement

11.5 Fuse and Reactor Specifications
Product (kW)
Single phase
0.4
200V
0.75
1.5
2.2
3-phase
0.4
200V
0.75
1.5
2.2
3.7
4
5.5
7.5
11
15
3-phase
0.4
400V
0.75
1.5
2.2
3.7
4
5.5
7.5
11
15
18.5
22
Only use Class H or RK5, UL listed input euses and UL listed circuit breakers. See the table above eor
the voltage and current ratings eor euses and circuit breakers.
AC Input Fuse
Current (A) Voltage (V) Inductance
10
600
15
20
10
15
20
32
50
50
63
80
100
10
15
20
32
35
50
63
70
100
Technical Specification
AC Reactor
Current(A) Inductance
(mH)
1.20
10
0.88
14
0.56
20
1.20
10
0.88
14
0.56
20
0.39
30
0.30
34
0.22
45
0.16
64
0.13
79
4.81
4.8
3.23
7.5
2.34
10
1.22
15
1.12
19
0.78
27
0.59
35
0.46
44
0.40
52
0.30
68
DC Reactor
Current (A)
(mH)
4
8.67
3
13.05
1.3
18.45
4
8.67
3
13.05
1.33
18.45
26.35
1.60
32
1.25
43
0.95
61
0.70
75
16
4.27
12
6.41
8
8.9
5.4
13.2
3.20
17
2.50
25
1.90
32
1.40
41
1.00
49
0.70
64
355