Engineering; Connection Terminals; Low-Voltage Side; Mains Voltage Side - Siemens RVL471 Basic Documentation

Heating and domestic hot water controller
Table of Contents

Advertisement

Siemens Building Technologies
HVAC Products
29

Engineering

29.1 Connection terminals

B9
B3
Ux B31
1
2
3
4
5
6
7
8
9
M
N
N
L
F1 Y1 F2 Y2
F3 Q1 Q3
F4 K4 F5 K5
1
2
3
4
5
6
7
8
9
29.1.1

Low-voltage side

DB
Data LPB
MB
Ground for LPB
A6
PPS (point-to-point interface), connection of room unit
MD
Ground for PPS
B9
Outside sensor
B1
Flow or boiler sensor
M
Ground for sensors, changeover contacts and signal output (e times)
B3
D.h.w. flow sensor
Ux
Heat demand signal
B31 Storage tank sensor / thermostat 1
B7
Return sensor (primary circuit)
H1
Changeover contact "Operating mode"
B32 Storage tank sensor / thermostat 2
B5
Room sensor
B71 Return sensor (secondary circuit)
H4
Minimum stroke limitation (Y
H3
Contact for locking the district heat parameters
In addition to the standard connection terminals, there is an auxiliary terminal M avail-
able.
29.1.2

Mains voltage side

N
Neutral conductor AC 230 V
L
Live conductor AC 230 V
F1/F4
Input for Y1/K4
Y1/K4 Heating circuit mixing valve OPEN / first burner stage
F2/F5
Input for Y2/K5
Y2/K5 Heating circuit mixing valve CLOSED / second burner stage
F3
Input for Q1 and Q3 / Y3
Q1
Heating circuit pump / circulating pump
Q3/Y3 Charging pump or diverting valve
F7
Input for Q4 and K6
Q4
Circulating pump
K6
Multifunctional relay
F6
Input for Y7 and Y8
Y7
D.h.w. mixing valve / valve OPEN
Y8
D.h.w. mixing valve / valve CLOSED
In addition to the standard connection terminals, there are 2 auxiliary terminals for N and
available.
Basic Documentation RVL471
29 Engineering
B7
B32
B5
B71
10
11
12
13
14
15
16
17
18
M
F7
Q4 K6 F6 Y7 Y8
Y3
10
11
12
13
14
15
16
17
18
contact)
min
19
20
19
20
105/118
CE1P2524E
23.10.2002