Heating Circuit Type 6 - Precontrol With District Heat; Plant Type 0 - No D.h.w; Plant Type 1 - D.h.w. Storage Tank With Charging Pump; Plant Type 2 - D.h.w. Storage Tank With Mixing Valve - Siemens RVL471 Basic Documentation

Heating and domestic hot water controller
Table of Contents

Advertisement

Siemens Building Technologies
HVAC Products
3.2.7
Heating circuit type 6 – precontrol with district heat
Y1
B7
Precontrol with district heat connection, with demand-compensated control of the sec-
ondary flow temperature acting on the valve in the primary return.
Heat demand signal from data bus. No heating program.
3.2.8
D.h.w. plant type 0 – no d.h.w.
The RVL471 does not provide d.h.w. heating.
3.2.9
D.h.w. plant type 1 – d.h.w. storage tank with charging
pump
M3
B31
K6
B32
Charging of d.h.w. storage tank through control of the charging pump. Acquisition of the
d.h.w. temperature with one or 2 sensors or thermostats. Circulating pump and electric
immersion heater are optional.
3.2.10
D.h.w. plant type 2 – d.h.w. storage tank with mixing
valve
Y7
B3
M3
K6
Charging of d.h.w. storage tank through control of the mixing valve according to own
temperature sensor in the storage tank flow. Acquisition of the d.h.w. temperature with
one or 2 sensors or thermostats. Circulating pump and electric immersion heater are
optional.
Basic Documentation RVL471
3 Fundamentals
N1
B71
1, 2
M4
B31
M4
B32
0, 5
19/118
CE1P2524E
23.10.2002