Siemens Building Technologies
HVAC Products
1
Summary
1.1
Brief description and key features
• The RVL471 is a multifunctional heating controller for use in residential and non-resi-
dential buildings that have their own d.h.w. heating facility
• Suited for:
−
Heating zone control with or without room influence via weather-compensated flow
temperature control
−
Precontrol via demand-compensated control of the main / secondary flow tem-
perature
−
Precontrol via demand-compensated boiler temperature control. Suited for integra-
tion into heat source cascades or heat generation systems (heat pump, solar,
wood)
• For use in plants with own heat generation or with a district heat connection
• With regard to d.h.w. heating, the RVL471 is suited for plants with d.h.w. storage tanks,
electric immersion heaters and instantaneous systems with own heat exchangers
• The RVL471 has 29 plant types preprogrammed. When a certain type of plant is se-
lected, all functions and settings required for that plant will be activated
• A scalable voltage output DC 0...10 V is used to pass the heat demand signal to other
systems
• A multifunctional relay provides additional control functions, if required
• For direct adjustment of the heating curve, the well known "bar" is used. Digital ad-
justment of the heating curve is possible also. A setting knob is used for making room
temperature readjustments
• All the other parameters are set digitally based on the operating line principle
• The RVL471 is capable of communicating with other units via LPB (Local Process Bus)
• Key design features: Operating voltage AC 230 V, CE conformity, overall dimensions
to DIN 43700 (144 x 144 mm)
1.2
Type summary
The RVL471 is a compact controller that requires no plug-in modules.
1.3
Equipment combinations
1.3.1
Suitable sensors
• For water temperatures:
Suitable are all types of temperature sensors that use a sensing element
LG-Ni 1000 7KH IROORZLQJ W\SHV DUH SUHVHQWO\ DYDLODEOH
−
Strap-on temperature sensor QAD22
−
Immersion temperature sensors QAE22...
−
Immersion temperature sensor QAP21.3 complete with connecting cable
• For the room temperature:
Suitable are all types of temperature sensors that use a sensing element
LG-Ni 7KH IROORZLQJ W\SHV DUH SUHVHQWO\ DYDLODEOH
−
Room temperature sensor QAA24
• For the outside temperature:
2XWVLGH VHQVRU 4$& VHQVLQJ HOHPHQW /*1L
−
−
Outside sensor QAC32 (sensing element NTC 575)
Basic Documentation RVL471
1 Summary
11/118
CE1P2524E