Boiler temperature controller (heat generation)
N2
Flow temperature controller (heating zone)
w
Setpoint of boiler temperature controller
N1
w
Setpoint of flow temperature controller
N2
∆w
Excess mixing valve temperature (set on controller N2)

11.5 Pulse lock

If, during a period of time that equals five times the running time, the actuator has re-
ceived only closing pulses, additional closing pulses delivered by the controller will be
locked. This minimizes the strain on the actuator.
For safety reasons, the controller delivers a one-minute closing pulse at 10-minute
intervals.
An opening pulse negates the pulse lock.
Basic Documentation RVL471
11 Function block "3-position actuator heating circuit"
w
w
N2 +
w
N2
w
N2