Setting Levels And Access Rights; Commissioning; Installation Instructions; Operating Lines - Siemens RVL471 Basic Documentation

Heating and domestic hot water controller
Table of Contents

Advertisement

Setting levels
Access rights
Operating line
"Plant type"
Other operating lines
Operating lines for func-
tional checks
Siemens Building Technologies
HVAC Products
Symbol
Plant information
Flow or boiler temperature
Room temperature
Outside temperature
Time of day
It is always the information selected last that is continuously displayed.
28.1.4

Setting levels and access rights

The operating lines are assigned to three different levels. Assignment and access are
as follows:
Level

Operating lines

End-user
1 to 50
Heating engineer
51 to 197
Locking level
198
• The enduser can access all analog operating elements. This means that he can select
the operating mode, set the heating curve, readjust the room temperature with the set-
ting knob, and activate manual operation.
Also, he can access operating lines 1 to 50
• The heating engineer can access all operating elements and all operating lines

28.2 Commissioning

28.2.1

Installation instructions

The RVL471 is supplied with Installation Instructions which give a detailed description
of installation, wiring and commissioning with functional checks and settings. They have
been written for trained specialists. Each operating line has an empty field in which the
selected value can be entered.
The Installation Instructions should not be thrown away after use but kept together with
the plant documentation.
28.2.2
Operating lines
The most important work to be performed when commissioning the plant is entering the
required type of plant. This entry activates all functions and settings required for the re-
spective plant type. Operating lines
All operating lines contain field-proven and practice-oriented values. Coding, guide val-
ues, explanations, etc., are given in the Installation Instructions where required.
Function block "25 Function" "Service functions and general settings" contains 4 oper-
ating lines that are especially suited for making functional checks:
• Operating line 161 permits simulation of the outside temperature
• On operating line 162, each of the output relays can be energized
• On operating line 163, all actual sensor values can be called up
• On operating line 164, all contacts H can be called up
Basic Documentation RVL471
28 Handling
Access
Press
or
together
Press
and
for three seconds
Press
and together until
appears; then, press
one after the other
,
,
and
103/118
CE1P2524E
23.10.2002

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents