6 Installation
Fig.17
Sample string
EN 14471 - T120 P1 W 1 O50 LI E U0
2
1
3
EN 1856-1 - T120 P1 W VxL40045 G(xx)
Tab.18
Overview of material properties
Version
Flue gas outlet

Material

Single-wall, rigid
Plastic
Stainless steel
Thick-walled,
aluminium
(1) according to EN 14471
(2) according to EN 1856
(3) according to EN 13501-1
32
6.4.1
Use the string on the flue gas outlet material to check whether it is suitable
for use on this appliance.
4
5
AD-3001120-01
Material properties
With CE marking
(1)
Temperature class T120 or
(2)
higher
Condensate class W (wet)
(2)
Pressure class P1 or H1
Fire resistance class E or bet­
ter
(3)
Important
With room-sealed operation, make sure the dirt trap in the boiler
air supply remains accessible. For example, fit a T piece with an
inspection trap in the air supply pipe directly above the boiler.
With a flue gas connection of two or more C 330 ECO boilers,
certain fan speeds need to be changed. Change the values of
relevant parameters for each boiler in the flue gas connection.
Set them to the values as specified in the parameter table for
the C 630 ECO boiler.
Material
1 EN 14471 of EN 1856–1: The material is CE approved according to
this standard. For plastic this is EN 14471, For aluminium and
stainless steel this is EN 1856-1.
2 T120: The material has temperature class T120. A higher number
is also allowed, but not lower.
3 P1: The material falls into pressure class P1. H1 is also allowed.
4 W: The material is suitable for draining condensation water
(W='wet'). D is not allowed (D='dry').
5 E: The material falls into fire resistance class E. Class A to D are
also allowed, F is not allowed. Only applicable to plastic.
Warning
The coupling and connection methods may vary depending on
the manufacturer. It is not permitted to combine pipes, coupling
and connection methods from different manufacturers. This also
applies to roof feed-throughs and common channels.
The materials used must comply with the prevailing regulations
and standards.
Air supply
Material
Plastic
Stainless steel
Aluminium
Material properties
With CE marking
Pressure class P1 or H1
Fire resistance class E or bet­
ter
(3)
7600532 - v.11 - 13122018