Material; Additional Guidelines - DeDietrich Innovens MCA 160 Manual

High-efficiency wall-hung gas boilers
Hide thumbs Also See for Innovens MCA 160:
Table of Contents

Advertisement

Tab.3
Flue gas outlet dimensions
Output (P)kW
Number of boil­
(80/60° C)
ers
294
2
441
3
588
4
735
5
882
6
1029
7
1176
8
7680446 - v.01 - 14082017
dia. D (mm)
H = 0 - 2 m
H = 2 - 5 m
180
185
215
220
260
265
300
300
330
335
360
365
390
390
5.3.6

Material

Warning
The coupling and connection methods may vary depending on
the manufacturer. It is not permitted to combine pipes, coupling
and connection methods from different manufacturers.
The materials used must comply with the prevailing regulations
and standards.
Tab.4
Flue gas outlet pipework materials
Design
(1)
Single-wall, rigid
Flexible
(1) The sealing must conform to pressure class 1
(2) With CE marking
Tab.5
Air supply pipework materials
Version
Single-wall, rigid
Flexible
5.3.7

Additional guidelines

For installing the flue gas outlet and air supply materials, refer to the in­
structions of the manufacturer of the relevant material. If the flue gas
outlet and air supply materials are not installed in accordance with the
instructions (e.g. not leakproof, not correctly bracketed), this can result
in dangerous situations and/or physical injury. After installation, check at
least all flue gas outlet and air supply parts for tightness.
Direct connection of the flue gas outlet to structural ducts is not permit­
ted because of condensation.
Always clean shafts thoroughly when using lining pipes and/or an air
supply connection.
H = 5 - 9 m
H = 9 - 13 m
190
195
225
235
270
275
305
310
340
340
370
370
395
400
Material
(2)
Thick-walled, aluminium
Plastic T120
Stainless steel
Plastic T120
Stainless steel
Material
Aluminium
Plastic
Stainless steel
Aluminium
Plastic
Stainless steel
5 Installation
H = 13 - 17 m
200
235
275
315
345
370
400
MCA
41

Advertisement

Table of Contents
loading

Table of Contents