Performing the full load test (DIEMATIC iSystem)
1. From the start page, press the
The EMISSION MESURMENTS menu appears on the display.
2. Turn the rotary button until PMAX is displayed.
3. Confirm the selection.
The boiler is now set to full load.
Checking/setting values for O
1. Measure the percentage of O
2. Compare the measured value with the checking values in the table.
Tab.37
Checking/setting values O
Values at full load for G20 (H gas)
C 330 ECO
C 630 ECO
(1) Nominal value
Caution
The O
values at full load must be lower than the O
2
load.
3. If the measured value is outside of the values given in the table,
correct the gas/air ratio.
7 Commissioning
key.
at full load
2
in the flue gases.
2
at full load for G20 (H gas)
2
O
4.3 - 4.8
4.3 - 4.8
values at low
2
(%)
(1)
2
(1)
(1)
51