Option 6 Remote Setpoint: Direct Wired Header Sensor & Modbus Setpoint Drive - Watts Aerco Benchmark Series Operation And Service Manual

Platinum boilers with edge controller
Hide thumbs Also See for Aerco Benchmark Series:
Table of Contents

Advertisement

Benchmark Platinum-Edge: Operation-Service Manual
SECTION 7 – BOILER SEQUENCING TECHNOLOGY
7.3.6 Option 6 Remote Setpoint: Direct Wired Header Sensor &
Modbus Setpoint Drive
OPTION 6 Instructions: Remote Setpoint, Direct Wired Header Sensor, Modbus Setpoint Drive
NOTE:
Both Header Sensor and Outdoor Sensor must be wired. See the Edge Controller Manual
for more information.
Step 1: HEADER SENSOR WIRING – ANY BOILER
1. Connect the Modbus Transmitter (P/N 65169) terminal Pin B to the I/O Board strip J3,
terminal 13 (BST RS485+) and Pin A to terminal 15 (BST RS485–) on any of the Boiler
units using Shielded pair 18 - 22 AWG cable.
2. Connect the shield to any Shield terminal, such as terminal 3 or 8 on strip J3.
3. Connect the Header Temperature Sensor (P/N 24410) to pins 2 and 3 of the Modbus
Transmitter using Shielded pair 18 - 22 AWG cable.
4. Install a jumper wire between pins 1 and 2 of the Modbus Transmitter.
NOTES:
Polarity must be observed for the RS485 connections.
Ground the shield to any Shield terminal on the I/O Board (such as Terminal 3 or 8).
The Header Sensor must be installed between 2 and 10 feet (0.61 and 3.1m)
downstream of the LAST boiler in the plant's supply water header.
There is no polarity to be observed. The ground for the shield is at the power supply
ground. The sensor end of the shield must be left free and ungrounded.
HEADER TEMP SENSOR
(P/N 24410)
Step 2: OUTDOOR SENSOR WIRING
1. If you have not already done so, complete the instructions above to connect the Modbus
Transmitter to the I/O Board.
2. Connect the Outdoor Temperature Sensor (P/N 61048) to Pins 3 and 6 of the Modbus
Transmitter using Shielded pair 18 - 22 AWG cable.
3. Install a jumper wire between Pins 4 and 5 of the Modbus Transmitter.
OUTDOOR TEMP SENSOR
(P/N 61048)
OMM-0137_D
• GF-211 •
7/16/2019
MODBUS TRANSMITTER
MODBUS TRANSMITTER
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
3 Shield
13 BST RS485+
15 BST RS485–
I/O BOARD STRIP J3
3 Shield
13 BST RS485+
15 BST RS485–
I/O BOARD STRIP J3