Watts Aerco Benchmark Series Operation And Service Manual page 46

Platinum boilers with edge controller
Hide thumbs Also See for Aerco Benchmark Series:
Table of Contents

Advertisement

Benchmark Platinum-Edge: Operation-Service Manual
SECTION 4 – INITIAL START-UP
PROPANE Combustion Calibration Instructions
Valve Position
Oxygen (O
BMK 2000
70%
6.5% ± 0.2%
50%
6.5% ± 0.2%
40%
6.5% ± 0.2%
30%
6.5% ± 0.2%
18%
5.5% ± 0.2%
BMK 2500
70%
5.4% ± 0.2%
45%
5.6% ± 0.2%
30%
6.0% ± 0.2%
22%
5.8% ± 0.2%
18%
6.0% ± 0.2%
BMK 3000
85%
5.2% ± 0.2%
65%
5.4% ± 0.2%
45%
6.0% ± 0.2%
30%
6.4% ± 0.2%
18%
6.4% ± 0.2%
TABLE 4-6b: PROPANE Final Valve Positions: BMK 5000 & 6000
Valve Position
Single-Fuel
Dual-Fuel
BMK 5000
70%
70%
50%
50%
40%
40%
30%
30%
18%
18%
BMK 6000
70%
85%
50%
65%
40%
45%
30%
30%
18%
18%
NOTE:
If NOx readings exceed the target values in Table 4-6a and 4-6b, increase the O
to 1% higher than the listed calibration range shown in the table. Record the increased O
value on the Combustion Calibration sheet.
OMM-0137_D
• GF-211 •
7/16/2019
) %
Nitrogen oxide (NOx)
2
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
Nitrogen Oxide
Oxygen (O
) %
2
5.5% ± 0.5%
<100 ppm
5.5% ± 0.5%
<100 ppm
5.5% ± 0.5%
<100 ppm
5.5% ± 0.5%
<100 ppm
6.0% ± 1.0%
<100 ppm
5.5% ± 0.5%
<100 ppm
5.5% ± 0.5%
<100 ppm
5.5% ± 0.5%
<100 ppm
5.5% ± 0.5%
<100 ppm
6.0% ± 1.0%
<100 ppm
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Carbon Monoxide (CO)
<150 ppm
<150 ppm
<150 ppm
<100 ppm
<100 ppm
<150 ppm
<150 ppm
<100 ppm
<100 ppm
<100 ppm
<150 ppm
<150 ppm
<150 ppm
<100 ppm
<100 ppm
Carbon
(NO
)
Monoxide (CO)
x
<150 ppm
<150 ppm
<150 ppm
<150 ppm
<150 ppm
<150 ppm
<150 ppm
<150 ppm
<150 ppm
<150 ppm
level up
2
2
Page 46 of 146