Option 8 Remote Setpoint: Modbus Header Temp Sensor & Modbus Setpoint Drive - Watts AERCO Benchmark OMM-0136 Operation And Service Manual

Natural gas, propane gas and dual fuel modulating & condensing boilers
Table of Contents

Advertisement

Benchmark Platinum-Edge [II]: Operation-Service Manual
SECTION 7 – BOILER SEQUENCING TECHNOLOGY
7.3.8 Option 8 Remote Setpoint: MODBUS Header Temp Sensor &
MODBUS Setpoint Drive
OPTION 8 Instructions: Remote Setpoint, Modbus Header Temp Sensor & Modbus Setpoint
Drive
HEADER TEMP SENSOR WIRING – ANY BOILER
Step 1:
MODBUS
1. Connect the Modbus Transmitter terminal Pin B to the I/O board strip J3, terminal 13
(BST RS485+) and Pin A to terminal 15 (BST RS485–) on any of the Boiler units using
shielded pair 18 - 22 AWG cable.
2. Connect the shield to any Shield terminal, such as terminal 3 or 8 on strip J3.
2. Connect the Header Temp Sensor to pins 2 and 3 of the Modbus Transmitter using
shielded pair 18 - 22 AWG cable.
3. Install a jumper wire between pins 1 and 2 of the Modbus Transmitter.
NOTES:
Polarity must be observed for the RS485 connections.
Ground the shield to any Shield terminal on the I/O board, such as terminal 3.
The Header Temp Sensor must be installed between 2 and 10 feet (0.61 and 3.1m)
downstream of the LAST boiler in the plant's supply water header.
There is no polarity to be observed. The ground for the shield is at the power supply
ground. The sensor end of the shield must be left free and ungrounded.
HEADER TEMP SENSOR
OMM-0137_E • GF-211 •
12/13/2019
MODBUS TRANSMITTER
Continued on next page
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
3 Shield
13 BST RS485+
15 BST RS485–
I/O BOARD STRIP J3
Page 103 of 153

Advertisement

Table of Contents
loading

Table of Contents