Condensate Drain Trap - Watts Aerco Benchmark Series Operation And Service Manual

Platinum boilers with edge controller
Hide thumbs Also See for Aerco Benchmark Series:
Table of Contents

Advertisement

Benchmark Platinum-Edge: Operation-Service Manual
SECTION 8 – MAINTENANCE

8.8 CONDENSATE DRAIN TRAP

All Benchmark Platinum boilers contain a condensate trap (P/N 24441), located external to the
unit and attached to the drain connection from the exhaust manifold at the rear of the unit. It
must be inspected for leaks and blockages and cleaned to ensure that condensate flows
normally.
A Condensate Trap O-Ring is included all 24 Month Maintenance Kits; instructions are in the
Technical Instruction Documents (TIDs) included with the kit.
3/4" NPT Port
Thumb
Screw
INLET
O-Rings
(2)
Figure 8-6: External Condensate Trap – Cross-Section & Exploded View
If your system includes a condensate neutralizer, the active ingredient must be replaced
periodically.
CONDENSATE
TRAP
CONDENSATE
NEUTRALIZER
OMM-0137_D
• GF-211 •
7/16/2019
CROSS-SECTION
Figure 8-7: Condensate Trap and Neutralizer
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
THUMB SCREWS (4)
COVER
CONDENSATE
TRAP O-RING
(P/N 84017)
FLOAT
OUTLET
3/4" NPT Port
EXPLODED
VIEW
Page 108 of 146

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF