SECTION 8 – MAINTENANCE
8.8 CONDENSATE DRAIN TRAP
All Benchmark Platinum boilers contain a condensate trap (P/N 24441), located external to the
unit and attached to the drain connection from the exhaust manifold at the rear of the unit. It
must be inspected for leaks and blockages and cleaned to ensure that condensate flows
normally.
A Condensate Trap O-Ring is included all 24 Month Maintenance Kits; instructions are in the
Technical Instruction Documents (TIDs) included with the kit.
3/4" NPT Port
Thumb
Screw
INLET
O-Rings
(2)
Figure 8-6: External Condensate Trap – Cross-Section & Exploded View
If your system includes a condensate neutralizer, the active ingredient must be replaced
periodically.
CONDENSATE
TRAP
CONDENSATE
NEUTRALIZER
OMM-0137_D
• GF-211 •
7/16/2019
CROSS-SECTION
Figure 8-7: Condensate Trap and Neutralizer