SECTION 6 – TROUBLESHOOTING
TABLE 10-1: Boiler Troubleshooting Procedures
Fault
Probable Causes
1.
Blower stopped running due to thermal or
current overload.
Blocked Blower inlet or inlet air filter.
2.
Blockage in Blower Proof switch.
3.
Blockage in Blocked Inlet switch.
4.
Defective Blower Proof switch.
5.
Defective Blocked Inlet switch.
6.
AIRFLOW
FAULT
DURING
Bad inlet air temperature sensor.
7.
IGNITION
Defective temperature sensor.
8.
Loose wire connection between the the
9.
Blower and the Controller.
Defective Air-Fuel Valve potentiometer.
10.
Hard light.
11.
OMM-0137_D
• GF-211 •
7/16/2019
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Corrective Action
1.
Check combustion blower for signs of excessive heat or high current
drain that may trip thermal or current overload devices.
Inspect the inlet to the combustion blower including the air filter at
2.
the air/fuel valve for signs of blockage.
Remove the Blower Proof switch and inspect for signs of blockage,
3.
clean or replace as necessary.
Remove the Blocked Inlet switch and inspect for signs of blockage,
4.
clean or replace as necessary.
Check the continuity of the Blower Proof switch with the combustion
5.
blower running. If there is an erratic resistance reading or the
resistance reading is greater than zero ohms, replace the switch.
Turn off unit and check the continuity of the Blocked Inlet switch. If
6.
there is an erratic resistance reading or the resistance reading is
greater than zero ohms, replace the switch.
Check the actual inlet air temperature reading and measure
7.
resistance at the Sensor Harness connection P1. Verify that the
reading conforms to the values shown in Section 2 of the
Benchmark Platinum-Edge: REFERENCE Manual (GF-212).
Refer to CORRECTIVE ACTION 7 and verify that the voltage
8.
conforms to the values shown in Section 2 of the Benchmark
Platinum-Edge: REFERENCE Manual (GF-212).
Check wire connection from the Blower motor to the Secondary
9.
Power Panel.
Check Air/Fuel Valve position at 0%, 50% and 100% open
10.
positions. The positions on the Valve Position bargraph should
match the readings on the Air/Fuel Valve dial.
Check igniter-injector for soot or erosion of electrode. Check
11.
injector solenoid valve to insure proper open/close operation.
Page 133 of 146