SECTION 7 – BOILER SEQUENCING TECHNOLOGY
OPTION 8 Instructions: Remote Setpoint, Modbus Header Sensor & Modbus Setpoint Drive
On the Manager only:
1. Go to Main Menu  Advanced Setup  BST Cascade, set the Parameters to the Values
in each menu in the table below.
Menu/Screen Name
Cascade
Configuration
Application
Configuration
Cascade Comm
OMM-0137_D
• GF-211 •
7/16/2019
Parameters
Unit Mode
Hdr Temp Sensor
Sensor Comm Address
Hdr Temp Point
Application
SH Operating Mode
Min address
Max address
Cascade Baud Rate
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Values
BST Manager
Network
240
14
Space Heating
Rmt Setpt Netwrk
The minimum unit address in the cascade
The maximum unit address in the cascade
The baud rate for the cascade.