Watts Aerco Benchmark Series Operation And Service Manual page 61

Platinum boilers with edge controller
Hide thumbs Also See for Aerco Benchmark Series:
Table of Contents

Advertisement

Benchmark Platinum-Edge: Operation-Service Manual
SECTION 5 – SAFETY DEVICE TESTING
HIGH Gas Pressure Test Instructions: BMK 3000 – 6000 ONLY
Alternative location
for manometer if hose
barb is preferred
NATURAL GAS HIGH Gas
Pressure Port
Install manometer here for High
Gas Pressure test
PROPANE Gas Pressure Port
Install manometer here for High Gas Pressure test
Alternative location for manometer
if hose barb is preferred
Figure 5-4b: High Gas Pressure Switch Locations & Test Ports – BMK 6000
OMM-0137_D
• GF-211 •
7/16/2019
NATURAL GAS HIGH GAS
PRESSURE SWITCH
- BMK 6000 – 10.5" W.C., 2.6 kPa
- BMK 5000 – 11.0" W.C., 2.7 kPa
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
DOWNSTREAM
SSOV WITH POC
SWITCH
PROPANE HIGH GAS
PRESSURE SWITCH
- BMK 6000 – 10.5" W.C., 2.6 kPa
- BMK 5000 – 4.5" W.C., 1.1 kPa
Page 61 of 146

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents