SECTION 7 – BOILER SEQUENCING TECHNOLOGY
OPTION 6 Instructions: Remote Setpoint, Direct Wired Header Sensor, Modbus Setpoint Drive
NOTES:
Polarity must be observed for the RS485 connections. The ground for the shield is at
the "SHLD" terminal in the I/O the Box.
When mounting the Outdoor sensor, it must be located on the North side of the building
where an average outside air temperature is expected. The sensor must be shielded
from direct sunlight as well as impingement by the elements. The outdoor sensor may
be wired up to 200 feet (61m) from the boiler.
There is no polarity to be observed. The ground for the shield is at the power supply
ground. The sensor end of the shield must be left free and ungrounded.
Step 3 – OPTION 6 CONFIGURATION
On All Boiler:
1. Go to: Main Menu
Set the Unit Mode parameter to BST Client.
2. Go to: Main Menu
Set the Unit Address parameter to the communication address of the unit.
On the Manager only:
1. Go to Main Menu  Advanced Setup  BST Cascade, set the Parameters to the Values
in each menu in the table below.
Menu/Screen Name
Cascade
Configuration
Application
Configuration
Cascade Comm
OMM-0137_D
• GF-211 •
7/16/2019
Advanced Setup
Advanced Setup
Parameters
Unit Mode
Hdr Temp Sensor
Application
SH Operating Mode
Min address
Max address
Cascade Baud Rate
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
BST Cascade
Cascade Configuration:
BST Cascade
Application Configuration:
Values
BST Manager
Header Temp
Space Heating
Rmt Setpt Netwrk
The minimum unit address in the cascade
The maximum unit address in the cascade
The baud rate for the cascade.
Page 94 of 146