Watts Aerco Benchmark Series Operation And Service Manual page 92

Platinum boilers with edge controller
Hide thumbs Also See for Aerco Benchmark Series:
Table of Contents

Advertisement

Benchmark Platinum-Edge: Operation-Service Manual
SECTION 7 – BOILER SEQUENCING TECHNOLOGY
OPTION 5 Instructions: Remote Setpoint, Direct Wired Header Sensor, 4-20ma Setpoint Drive
Step 3: OPTION 5 CONFIGURATION
On All Boiler:
1. Go to: Main Menu
Set the Unit Mode parameter to BST Client.
2. Go to: Main Menu
Set the Unit Address parameter to the communication address of the unit.
On the Manager only:
1. Go to Main Menu  Advanced Setup  BST Cascade, set the Parameters to the Values
in each menu in the table below.
Menu/Screen Name
Cascade
Configuration
Application
Configuration
Cascade Comm
* Be sure that the SW1-4 DIP switch on Controller's Interface Board is set appropriately (On = Current,
Off = Voltage.)
OMM-0137_D
• GF-211 •
7/16/2019
Advanced Setup
Advanced Setup
Parameters
Unit Mode
Hdr Temp Sensor
Application
SH Operating Mode
BST Remote Signal
Min address
Max address
Cascade Baud Rate
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
BST Cascade
Cascade Configuration:
BST Cascade
Application Configuration:
Values
BST Manager
Header Temp
Space Heating
Rmt Setpt Analog
4-20mA/1-5V *
The minimum unit address in the cascade
The maximum unit address in the cascade
The baud rate for the cascade.
Page 92 of 146