Benchmark Platinum-Edge: Operation-Service Manual
SECTION 7 – BOILER SEQUENCING TECHNOLOGY
OPTION 1 Instructions: Constant Setpoint with Direct Wired Header Sensor
On the Manager only:
1. Go to Main Menu Advanced Setup BST Cascade, set the Parameters to the Values
in each menu listed in the table below.
Menu/Screen Name
Cascade
Configuration
Application
Configuration
Cascade Comm
OMM-0137_D
• GF-211 •
7/16/2019
Parameters
Unit Mode
Hdr Temp Sensor
Application
SH Operating Mode
Outdoor Temp Sensor
Plant Setpoint
Min address
Max address
Cascade Baud Rate
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Values
BST Manager
Header Temp
Space Heating
Constant Setpoint
Outdoor Sensor
Header temperature required for the cascade
The minimum unit address in the cascade
The maximum unit address in the cascade
The baud rate for the cascade.
Page 84 of 146