Condensate Drain Trap - Watts Aerco Benchmark BMK750 Operation And Service Manual

With edge i controller
Hide thumbs Also See for Aerco Benchmark BMK750:
Table of Contents

Advertisement

Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 8 – MAINTENANCE

8.7 CONDENSATE DRAIN TRAP

All Benchmark boilers contain a condensate trap (P/N 24441), located external to the unit,
attached to the exhaust manifold's drain at the rear of the unit.
This trap must be inspected for leaks and blockages, cleaned to ensure that the float is free to
move, and condensate flows normally, and the O-Ring (P/N 84017 included in all 24 Month
Maintenance Kits) replaced if it is worn or damaged. In addition, you must ensure the vent
(under the removable cover) is free and clear of obstructions.
Thumb
Screw
3/4" NPT Port
INLET
EXPLODED VIEW
Figure 8-6: External Condensate Trap – Cross-Section & Exploded View
If your system includes a condensate neutralizer, the active ingredient must be replaced
periodically.
CONDENSATE
TRAP
CONDENSATE
NEUTRALIZER
OMM-0145_D • GF-218 •
11/2/2020
THUMB SCREWS (4)
Figure 8-7: Condensate Trap and Neutralizer
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
COVER
O-RING
(P/N 84017)
O-Rings
(2)
3/4" NPT Port
OUTLET
FLOAT
CROSS-SECTION
Page 140 of 213
VENT