KNX
Push button sensor 3
Mount the double-height push button sensors on two appliance boxes with a second support
ring . For mounting on an appliance box, use the enclosed screw/anchor set.
o
Carefully remove the rocket covers (9) and inscription signs (8) from the push button
sensor (6).
o
Attach the frame (5) to the bus coupler (4).
o
Carefully attach the push button sensor (6) to the bus coupler (4).
o
Screw the push button sensor to the support ring of the bus coupler module. Use the
locking screw (7) provided.
o
Screw the double-height push button sensors to the lower support ring of the anchors (11).
Use the screws (12) provided.
o
If possible load the physical address into the device before final mounting (see chapter 5.2.
Commissioning).
o
If necessary, label the inscription signs (8).
o
Mount the inscription signs (8) and the rocker covers (9).
5.2 Commissioning
Loading the physical address and application software
The programming button and -LED (10) are located under the topmost rocker cover.
The topmost rocker cover is dismantled.
i If the device does not receive any application software, or the wrong application software,
then the backlighting flashes.
o
Press the Programming button (10).
The programming LED lights up.
o
Assign physical address.
The programming LED goes out.
o
Load the application software into the device.
o
Mount the inscription panel (8) and the rocker cover (9).
6 Appendix

6.1 Technical data

KNX medium
Commissioning mode
Rated voltage
Power consumption
Connection mode
Protection class
Ambient temperature
Storage/transport temperature
6.2 Accessories
Second support ring
Inscription sheet
Inscription sheet
Bus coupler 3
Rocker set 1-gang
Rocker set 2-gang
Rocker set 3-gang
Rocker set 4-gang
Rocker set 6-gang
32574912
10410684
24.02.2016
DC 21 ... 32 V SELV (Via bus coupler 3)
typical 150 mW (Via bus coupler 3)
10 pole male connector strip
TP
S-mode
III
-5 ... +45 °C
-20 ... +70 °C
Order No. 1127 00
Order No. 1089 00
Order No. 1090 00
Order No. 2008 00
Order No. 2131 ..
Order No. 2132 ..
Order No. 2133 ..
Order No. 2134 ..
Order No. 2136 ..
4/5

Advertisement

loading

This manual is also suitable for:

5112 005133 005134 005136 005113 005131 00 ... Show all