Setting Frequency By Current Reference Input - YASKAWA VS-606V7 Series Instruction Manual

Compact general-purpose inverter
Hide thumbs Also See for VS-606V7 Series:
Table of Contents

Advertisement

• Setting Frequency by Current Reference Input

When setting frequency by inputting
current reference (4-20mA or 0-20mA)
from the control circuit terminal FR,
switch the DIP switch SW1 on the control
circuit board to "I" side.
SW1 is accessed by removing the digital
operator.
Never input voltage reference to control circuit terminal FR when DIP switch
NOTE
SW2 is switched to "I" side. This could damage the inverter.
Initial setting of multi-function output terminal
No.
n057
n058
n059
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Terminals
Initial Setting
MA, MB
0 (fault)
P1
1 (in operation)
P2
2 (Frequency agreed)
83