• Coast to stop
Example: when accel/decel time 1 is selected
* When frequency reference is changed during running.
Upon removal of the FWD (REV) run command, the motor starts coasting.
Applying DC injection braking
• DC injection braking current (n089)
Sets DC injection braking current in units of 1%. (Inverter rated current=100%)
• DC injection braking time at stop (n090)
Sets the DC injection braking time at stopping in units of 0.1 second. When the
setting of n090 is 0, DC injection braking is not performed but inverter output is
shut OFF at the timing of DC injection braking start.
When coasting to a stop is specified in stopping method selection (n005), DC injection
braking at stop does not operate.
72