YASKAWA VS-606V7 Series Instruction Manual page 107

Compact general-purpose inverter
Hide thumbs Also See for VS-606V7 Series:
Table of Contents

Advertisement

• Energy-saving voltage lower/upper limit (n141, n142, n159,
n160)
Sets the upper and lower limits of the output voltage. When the value calculated in
the energy-saving control mode is larger than the upper limit (or smaller than the
lower limit), the value is output as a voltage reference value. The upper limit is set
to prevent over-excitation, and the lower limit is set to prevent stalls when the load
is light. The voltage limit is set for machines using 6Hz/60 Hz. For any voltage
other than 6Hz/60Hz, set the (value of the) voltage limit according to linear
interpolation. The parameters are set in % for 200V/400V inverters.
Parameters
No.
Energy-saving voltage
n141
lower limit (60 Hz)
Energy-saving voltage
n142
lower limit (6 Hz)
Energy-saving voltage
n159
upper limit (60 Hz)
Energy-saving voltage
n160
upper limit (6 Hz)
*Doubled for the 400V class inverters.
106
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Setting
Name
Unit
Range
%
0 to 120
%
0 to 25
%
0 to 120
%
0 to 25
Initial
Setting
50
12
120
16