• Setting necessary parameters for communication
Communication related parameters must be set for PLC communication. parameters
n151 to n157 cannot be set during communication. Always set them prior to
performing communication.
Parameter
Name
n003
Run command selection
Frequency reference
n004
selection
Timeover detection
selection
Monitors transmission time
n151
between the receiving the
correct data from the PLC
(Timeover: 2 sec)
Communication frequency
n152
Reference monitor unit
selection
n153
Slave address
n154
Baud rate selection
n155
Parity selection
n156
Sending waiting time
n157
RTS control
* The slave does not respond to the command from the master when set to 0.
Monitoring run status from the PLC, setting/referencing of parameters, fault reset and
multi-function input reference can be done regardless of run command or frequency
reference selection.
Multi-function input reference from PLC becomes OR with input commands from S1
to S7 multi-function input terminals.
94
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
0 : operator
1 : control circuit terminals
2 : communication
3 : communication card (optional)
0 : Local potentiometer (digital operator)
1 : frequency ref. 1 (n024)
2 : control circuit terminals (voltage 0 to 10V)
3 : control circuit terminals (current 4 to 20mA)
4 : control circuit terminals (current 0 to 20mA)
5 : pulse train
6 : MEMOBUS communication (Register No. 000211)
7 : operator circuit terminals (voltage 0 to 10V)
8 : operator circuit terminals (current 4 to 20mA)
9 : communication card (optional)
0 : timeover detection (free run stop)
1 : timeover detection (coasting to a stop with speed
reduction time 1)
2 : timeover detection (coasting to a stop with speed
reduction time 2)
3 : timeover detection (continuous operation, warning
display)
4 : timeover detection not provided
0 : 0.1Hz
1 : 0:0.1Hz
2 : 30000/100% (30000 = max. output frequency)
3 : 0.1%
Setting range: 0 to 32*
0 : 2400 bps
1 : 4800 bps
2 : 9600 bps
3 : 19200 bps
0 : even parity
1 : odd parity
2 : no parity
Setting limit: 10 ms to 65 ms setting unit: 1 ms
0 : RTS control
1 : no RTS control (RS-422A 1 to 1 communication)
Initial
Setting
0
0
0
0
0
2
0
10 ms
0