YASKAWA VS-606V7 Series Instruction Manual page 100

Compact general-purpose inverter
Hide thumbs Also See for VS-606V7 Series:
Table of Contents

Advertisement

• Monitor Data (available only for read out)
Register No.
0020H
0021H
0022H
0023H
0024H
0025H-026H
0027H
0028H
0029H
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
bit
Description
0
Run command
1 : Run
1
Reverse run
1 : Reverse run
2
Inverter operation ready
1 : Ready
3
Fault
1 : Fault
4
Data setting error
1 : Error
5
Multi-function output 1
(1 : MA ON
6
Multi-function output 2
(1 : P1 ON
7
Multi-function output 3
(1 : P2 ON
8-F
(Not used)
0
Over current (OC)
1
Over voltage (OV)
2
Inverter overload (OL2)
3
Inverter overheat (OH)
4
(Not used)
5
(Not used)
6
PID Feedback loss (FbL)
7
External fault (EF, EFO)
Emergency stop (STP)
8
Hardware fault (Fxx)
9
Motor overload (OL1)
A
Overtorque detection (OL3)
B
(Not used)
C
Power loss (UV1)
D
Control power fault (UV2)
E
MEMOBUS communications timeover (CE)
F
Operator connection (OPR)
0
Data write in
1
(Not used)
2
(Not used)
3
Upper/lower limit fault
4
Consistency fault
5-F
(Not used)
Frequency reference (Unit : n152)
Output frequency (Unit : n152)
(Not used)
Output current (10/1A)
Output voltage reference (1/1V)
0
Load short circuit (SC)
1
Ground fault (GF)
2
Input open phase (PF)
3
Output open phase (LF)
4
Installed type braking resistor overheat
5
Braking transistor fault (RR)
6-F
Not used
0 : Stop
0 : Forward run
0 : Not ready
0 : MA OFF)
0 : OFF)
0 : OFF)
99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents