• Message format
For communications, the master (PLC) sends a command
to the slave (VS-606V7) and the slave responds to it. The
configuration for sending and receiving is as shown to the
right. The length of the data varies according to the
contents of commands (functions).
The interval between messages must be maintained at the
following amount.
• Slave address: Inverter address (0 to 32). Setting to 0 indicates simultaneous
broadcasting. The inverter does not respond to the command from the master.
• Function code: Command codes (See below).
Function
Code
01H
08H
10H
• Data: Composes a series of data by combining holding register numbers (test codes
for loop-back numbers) and their data. Data length depends on the contents of the
commands.
• Error check: CRC-16 (Calculate the value by the following method.)
1. The default value at calculation of CRC-16 is normally 0. In the MEMOBUS
system, change the default to 1 (all 1 to 16-bit).
2. Calculate CRC-16 assuming that the loop address LSB is MSB and the last data
MSB is LSB.
3. Also calculate CRC-16 for a response message from the slave and refer it to
CRC-16 in the response message.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
VS-606V7
VS-606V7
VS-606V7
Reference Message
Function
Minimum (Byte) Maximum (Byte) Minimum (Byte) Maximum (Byte)
Reading holding
8
8
resistor contents
Loop back test
8
8
Write in several
11
41
holding resistors
Slave address
Function code
Data
Error Check
Response Message
7
37
8
8
8
8
95