Error Handling - Siemens SIMATIC PCS 7 Function Manual

Process control system, advanced process functions apf
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Storage location management
5.2 FB_SACT
In/out parameters
The following table shows the input and output parameters of the "FB_SACT" block:
Parameter
OP_REC_W
APF_AS
APF_OS
5.2.5

Error handling

Errors occurring in the block are signaled via an integrated "ALARM_8P" block and displayed
at the digital outputs of the block. They can be analyzed by the requesting block on the basis
of the output structure. The error bits are available at the block as output signals.
The following error messages can be generated:
Request
structure
MON_ERR
82
Description
Operator: 1 = Data request
APF function block version in AS
APF function block version in OS
Output
QCNT_ERR
Error, invalid IN_COUNT request parameter,
IN_COUNT <= 0 or > 10
QBOOLERR
Error, invalid "IN_CNTxx" request parameter,
IN_CNT... < 0 or > 15
QINDBERR
Instance DB error;
no instance data block or insufficient data length
QLEN_ERR
Error
Maximum data cell size exceeded,
data cell > 16230 bytes
QPARAMF
Parameter assignment error;
ID or TIME_MON <= 0 or ARCH_NA not specified
QERR
Data error
REQ_ID in request and receive structure not the same
QMONERR
Runtime error; monitoring timeout
QWM_ERR
Error from FB_UA_W: Data error,
job data in WinCC communication interface do not correspond to
original job data
QWM_AERR
Error from FB_UA_W: Archive error;
job data in the WinCC communication interface reset by the OS, or
script error in the OS
QWM_CERR
Error from FB_UA_W: Communication error;
Error message from "BSEND" coupling blocks
QWM_PERR
Error from FB_UA_W: Parameter assignment error;
incorrect ID_1, R_ID_1 or ID_2, R_ID_2 or duplicate REQ_ID
Type
BOOL
WORD
WORD
Meaning
Advanced Process Functions (APF)
Function Manual, 07/2016, A5E38719883-AA
Default
0
0
0

Advertisement

Table of Contents
loading

Table of Contents