Storage location management
5.5 FB_STMAT
Parameter
EN_SEAR
Operator control enable: Search
EN_POS
Operator control enable: Selected row number
DIS_MAAU
1 = Display of manual / auto buttons in the face‐
plate
DIS_SEAR
1 = Display of search button in the faceplate
QPOS
Selected row number
ALARM_ST
ALARM structure for connection of an external
message block
MSG_STAT
ALARM_8P: STATUS
MSG_ACK
ALARM_8P: ACK_STATE
QMSG_SUP
ALARM_8P: 1 = Message suppression active
QMSG_ERR
ALARM_8P: ERROR
In/out parameters
The following table shows the in/out parameters of the "FB_STMAT" block:
Parameter
OPMANAUT
Operator: 0 = manual, 1 = auto
OPSEARCH
Operator: 1 = Search
OP_POS
Operator: Row number selection
ROW_SEL
Selected rows (storage locations)
APF_AS
APF function block version in AS
APF_OS
APF function block version in OS
5.5.5

Error handling

Block error
Errors occurring in the block are signaled via an integrated "ALARM_8P" block and displayed
at the digital outputs of the block. They can be analyzed by the requesting block on the basis
of the output structure. The error bits are available at the block as output signals.
The following error messages can be generated:
Request struc‐
118
Description
Description
Output
ture
QPARAMF
QRLENERR
Type
BOOL
BOOL
BOOL
BOOL
INT
UDT_ALARM_ST
WORD
WORD
BOOL
BOOL
Type
BOOL
BOOL
INT
WORD
WORD
WORD
Parameter assignment error;
ID=0 or ARCH_NA=' ' or TIME_MON=0 or
with activated filter (EN_FILT = 1): Filter ID < 0 or
when use of remainder is activated (EN_REM = 1):
SPLIT_PT < 1 / >9 or LFILTER2 < 0 or SP_MODE = 0
Data block length of the receive data is not correct
Default
0
0
0
0
0
0
0
0
0
Default
0
0
0
16#0
0
0
Meaning
Advanced Process Functions (APF)
Function Manual, 07/2016, A5E38719883-AA
OS tag
x
x
x
x
x
-
-
-
-
-
OS tag
x
x
x
x
x
x

Advertisement