Fb_Archiving_Xxx - Siemens SIMATIC PCS 7 Function Manual

Process control system, advanced process functions apf
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Archive management
8.3 User archives
8.3.3

FB_ARCHIVING_XXX

Up to 2000 archive data records and their values are saved in each of the
"FB_ARCHIVING_XXX" user archives. There are two types of archives when using the
engineering tool.
Depending on the type of archive group defined with the APF Engineering Tool and saved in
the "FB_ARCHIVGROUP" user archive, the "FB_ARCHIVING_XXX" can be used as follows:
● Batch-based archiving
● Archiving freely-definable data
Batch-based archiving
The archive has the following structure:
REC_ID
REC_READ
REC_EXPORTED
REC_FINISHED
REC_PREPARED
BA_NA
BA_ID
TIME_START
TIME_END
SOURCE
SOURCE_ID
DEST
DEST_ID
MAT_NAME
MAT_ID
MLOT_NAME_SRC
MLOT_ID_SRC
MLOT_NAME_DST
MLOT_ID_DST
MLOT_NAME_DST_OLD Previous material lot
MLOT_ID_DST_OLD
SP
PV
UOM
PRC_NA
PARAMSET
PARAMSET_ID
230
Element
Internal ID of archive data record
Job data read
(MES)
Job data exported
(C function > csv file)
Job completed
Read enable
(MES)
Batch name
Batch ID
Start time of the job
End time of the job
Source
ID of the source
Name of the destination
ID of the destination
Material
ID of the material
Material lot source
ID of the material lot source
Material lot destination
ID of the material lot destination
ID of previous material lot
Overall setpoint
Actual value (MLOT-based)
Unit of the setpoint/actual value
Procedure name
Parameter set
ID of the parameter set
Description
Function Manual, 07/2016, A5E38719883-AA
Format
INTEGER 32
BOOL
BOOL
BOOL
INTEGER 32
STRING 32
INTEGER 32
DATE
DATE
STRING 64
INTEGER 32
STRING 64
INTEGER 32
STRING 64
INTEGER 32
STRING 64
INTEGER 32
STRING 64
INTEGER 32
STRING 64
INTEGER 32
DOUBLE
DOUBLE
STRING 16
STRING 32
STRING 64
INTEGER 32
Advanced Process Functions (APF)