I/Os - Siemens SIMATIC PCS 7 Function Manual

Process control system, advanced process functions apf
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Storage location management
5.2 FB_SACT
...
IN_DB..., requested value y
5.2.4

I/Os

Input parameters
The following table shows the input parameters of the "FB_SACT" block:
Parameter
SAMPLE_T
RUNUPCYC
ID
ARCH_NA
IN_DB01
to
IN_DB25
IN_COL01
to
IN_COL10
IN_FOR01
to
IN_FOR10
IN_OFF01
to
IN_OFF10
IN_CNT01
to
IN_CNT10
IN_COUNT
COUNT
TIME_MON
W_REC_ST
RESET
MSG_EVID
80
CELL
...
Requested format
Description
Sampling time [s]
Number of startup cycles
ID of the block
Archive name
Number of FB_STOR instance data block for
storage locations 1 to 25
Column in user archive for values 1 to 10
Format ID for values 1 to 10
Offset for values 1 to 10
Position of binary values 1 to 10
Number of values to be transferred per stor‐
age location
Number of send trigger repetitions if an error
occurs
Monitoring time
Input structure with job feedback from
FB_UA_WM
Reset data
ALARM_8P: EV_ID
FORMAT
Bytes
...
Depends on for‐
mat
REAL
INT
INT
STRING[16]
DINT
DINT
DINT
DINT
WORD
DINT
INT
REAL
UDT_UA_W_ST
BOOL
DWORD
Function Manual, 07/2016, A5E38719883-AA
Address
...
...
Maximum of 16229
Type
Default
1
10
0
''
0
0
0
0
0
0
1
30.0
0
0
Advanced Process Functions (APF)