Storage location management
5.5 FB_STMAT
"MODE" parameter
You can define the mode of the block using the input word "MODE":
Bit
0
EDGE_START_NEC
1
QSEL_ERR_MSG
2
QRUN_ERR_MSG
"OP_EN" parameter
You can enable button operation in the faceplate with the input word "OP_EN". This enable is
only effective if the mode allows button operation.
Bit
0
AUT
1
MAN
2
3
POSITION
4
SEARCH
"HIDE_BUT" parameter
You can hide buttons in the faceplate with the input word "HIDE_BUT".
Bit
0
MANAUT
1
2
SEARCH
Output parameters
The following table shows the output parameters of the "FB_STMAT" block:
Parameter
QREC_R
Status of read data request
QRUN_UP
Status display startup active = 1
112
Name
0 = Positive edge at the "L_START" input required.
1 = No positive edge at the "L_START" input required.
0 = OS QSEL_ERR message deactivated
1 = OS QSEL_ERR message is active
0 = OS QRUN_ERR message deactivated
1 = OS QRUN_ERR message is active
Name
0 = "Auto" operation disabled
1 = "Auto" key, external enable for operation
0 = "Manual" operation disabled
1 = "Manual" key, external enable for operation
not used
0 = "Storage location selection" operation disabled
1 = "Storage location selection", external enable for operation
0 = "Search" operation disabled
1 = "Search" key, external enable for operation
Name
0 = "Auto" and "Manual" are shown
1 = "Auto" and "Manual" are hidden
not used
0 = "Search" is shown
1 = "Search" is hidden
Description
Meaning
Meaning
Meaning
Type
INT
0
BOOL
0
Advanced Process Functions (APF)
Function Manual, 07/2016, A5E38719883-AA
Default
OS tag
x
-