5. Internal Memory Configuration and Functions
5.3. Operation parameters setting area
4.
Use I/O parameter window for more convenient setting.
Figure 47 – I/O Parameter window 6 (average value)

Scaling type (address 18)

1.
Bit 0 to 3 of memory address 16 is used to specify the scaling type parameter.
2.
If the bit is set to '1', the scale range will be an unsigned integer type (Unipolar)
with the output data range of 0 – 65535 by scaled calculation.
3.
If the bit is set to 0, the scale range will be signed integer type (Bipolar) with the
output data range of -32768 – 32767 by scaled calculation (default).
4.
Information specified in Bits 4–F will be disregarded.
96
Resistance Temperature Detector 2MLF-RD4A User's Guide
Figure 48 – Scaling type