5. Internal Memory Configuration and Functions
5.2. Internal memory functions
The flag can be set for the input variation in terms of quantity as well as rate of change.

Temperature value (internal memory address %UWa.b.4 ~7)

1.
Temperature-converted (measured temperature) value of each channel is stored as
shown below.
2.
Range of the output (measured) temperature value based on sensor type is as
follows:
Sensor
type
Pt100
84
Resistance Temperature Detector 2MLF-RD4A User's Guide
Figure 30 – Rate of change alarm flag
Figure 31 – Temperature-converted value
Address
%UWa.b.4
CH0 Temperature Value
%UWa.b.5
CH2 Temperature Value
%UWa.b.6
CH2 Temperature Value
%UWa.b.7
CH3 Temperature Value
Output range
2100 – 8600
(-210.0°C – 860.0°C)
Honeywell
Description
Effective measuring range
2000 – 8500
(-200.0°C – 850.0°C)
Remarks
_
R200
September 2010