Scaled Temperature Output Value (Internal Memory Address %Uwa.b.8~11); Temp Maximum/Minimum Value (Internal Memory Address %Uwa.b.12 ~19); Figure 32 - Scaling Value - Honeywell 2MLF-RD4A User Manual

Resistance temperature detector
Table of Contents

Advertisement

Sensor
type
JPt100

Scaled temperature output value (internal memory address %UWa.b.8~11)

1.
Scaling value of the specified channel is stored as shown below. The scaling value
depends on the range of the maximum value and the minimum value selected by the
user.
Refer to Table 8 which specifies the scaled temperature values. (See Specifications
for details on the scaling function.)

Temp maximum/minimum value (internal memory address %UWa.b.12 ~19)

1.
Maximum/minimum temperature value is the output when the command to search
for maximum/minimum is 1. (See Specifications for details on its functions.)
R200
Resistance Temperature Detector 2MLF-RD4A User's Guide
September 2010
5. Internal Memory Configuration and Functions
Output range
-2100 – 6500
(-210.0°C – 650.0°C)
Figure 32 – Scaling value
Address
%UWa.b.8
CH0 Scaling Value
%UWa.b.9
CH1 Scaling Value
%UWa.b.10
CH2 Scaling Value
%UWa.b.11
CH3 Scaling Value
Honeywell
5.2. Internal memory functions
Effective measuring range
-2100 – 6400
(-200.0°C – 640.0°C)
Description
Remarks