Rs-485 Configuration; Pre-Requisites; Bacnet Configuration; Pre-Requisties - Honeywell TR50 User Manual

Indoor air quality sensor
Hide thumbs Also See for TR50:
Table of Contents

Advertisement

DIP Switch (Address settings) : For the Sylk
configure "1,2,4 and 8" address. Do not configure "16 to 128" address.

4.3 RS-485 Configuration

4.3.1 Pre-Requisites:

Before configuring the device make sure the power supply is Switch OFF.
Refer

4.4 BACnet Configuration

4.4.1 Pre-Requisties

Adjust the switches on the back of the device to enable the device to operate in
BACnet mode. Refer

4.4.2 Automatic MAC Address

The TR50 IAQ Sensor device support automatic MAC address when DIP switch
address is put to all OFF or all ON.
17
Default Address = 1
Power Source (24 VAC/VDC) to connect TR50 device and Plant controller/
Unitary controller
RS-485 cables
Plant controller/ Unitary controller
Wiring Connections
Dip Switch Configuration
TM
1 2 4 8
Default: 1
Address: 1
Address: 2
Address: 3
Address: 4
Address: 5
Address: 6
Address: 7
Address: 8
section on page 9 for details about RS-485 wiring.
Bus device address always
1 2 4 8
Address: 9
Address:10
Address:11
Address:12
Address:13
Address:14
Address:15
for more details.
TR50 - User Guide