Type-0 Embedded Logic; Type-1 Embedded Logic - Honeywell H-S81-HS Manual

Safety bus
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

System Components
Channel Function
Ch1
Ch2
Ch3
Ch4
Ch5
Ch6
Ch7
Ch8

Type-0 Embedded Logic

If this type of embedded logic is selected, the module will not execute an internal logic when it is
isolated from the control panel (backup mode).
NOTE: Type-0 embedded logic can only be set in I/O Mode operation.

Type-1 Embedded Logic

This type of embedded logic is typical of extinguishing/release systems with one group of cylinders
or one release solenoid valve.
43
Manual Discharge/Primary
Discharge
Sequence Stop (Hold)
Inhibit Discharge
Automatic Disabled
Cylinder Pressure Low (PSL)
Main/Reserve
Secondary Discharge
System Tripped (PSH)
Automatic-1
Automatic-2
Table 3.2 Input Configuration Parameters
Channel
Function
Ch9
EV
Ch10
EV
EV
Ch11
TOA
TO
EV
Ch12
TOA
TO
TOA
Ch13
TO
TOA
Ch14
TO
Ch15
V15
Table 3.3 Output Configuration Parameters
Logic
Alarm test
Latched/NA
Disabled
Not
Disabled
Latched/NA
Not
Disabled
Latched/NA
Not
Disabled
Latched/NA
Latched/NA
Disabled
Not
Disabled
Latched/NA
Latched/NA
Disabled
Latched/NA
Disabled
Enabled/
Latched/NA
Disabled
Enabled/
Latched/NA
Disabled
Mode
Fixed-De-energized
Fixed-De-energized
Fixed-De-energized
Periodical
Fixed-De-energized
Fixed-De-energized
Periodical
Fixed-De-energized
Periodical
Fixed-De-energized
Periodical
Fixed-De-energized
Fixed-De-energized
Safety Bus Manual — P/N LS10177-000HI-E:B 02/21/2019
SB-ECM Module
Alarm
Automatic
Signal
delay
reset
0 sec.
Fire
No
0 sec.
Supervisory
No
0 sec.
Supervisory
No
0 sec.
Supervisory
No
0 sec.
Supervisory
No
0 sec.
Supervisory
No
0 sec.
Fire
No
0 sec.
Fire
No
0 sec.
Fire
No
0 sec.
Fire
No
Sounder
No
No
No
Yes
No
No
Yes
No
Si
No
Yes
No
No