Preparation; Programming The System - Siemens FC700A Installation And Hardware Commissioning

Fire detection system
Hide thumbs Also See for FC700A:
Table of Contents

Advertisement

Commissioning
4.2

Preparation

4.3

Programming the system

14
Building Technologies
Fire Safety & Security Products
Control unit FC700A
Connect mains cable and supply line (2)
Install possible additional modules chassis and attach connection cable in ac-
cordance with the system documentation
Set I-Bus address on all modules / set switches and jumpers
If existing, insert EPROM on C-Bus gateway FG700A (E3H020)
Insert all modules
Attach I-Bus flat cable and supply cable 5V/24V on all I-Bus modules, see
chapter 5
Connect fire control installations
Connect batteries
Control terminal FT700A
Insert inscription strips
Connect C-Bus and supply line in accordance with the system documentation
Install terminal
Floor repeater panels
Set LON-Bus address / set switch
Remove resistor if necessary
Parallel indicator panel
Set device address / if necessary remove resistor array
First switching-on
Apply mains voltage, observe the safety regulations in Chapter 2
Start-up process -> see chapter 16
Programming the system -> see SWE700A Online Help.