B3Q700 Control Terminal For Use As 'Fc' Or 'Ft - Siemens FC700A Installation And Hardware Commissioning

Fire detection system
Hide thumbs Also See for FC700A:
Table of Contents

Advertisement

B3Q700 Control terminal for use as 'FC' or 'FT'

6
B3Q700 Control terminal for use as 'FC' or 'FT'
Pos.
Module
1
Flash ROM
2
Protective cover
3
Programming switch 'S5-2': Event memory
overflow blocking
4
Resistors 'R49/50'/'R31'...'R34':
Adjust C-Bus impedance
5
Jumper 'X30': 'C-Bus potential'
6
0Ω resistors 'X31'... 'X34'
7
Inscription set FCA7xx
8
Plug-in terminals 'K5'/'K6'/'K7'
9
(Option) RS232 interface card E3I020 with
mounting accessories Z1B020
2
7
1
2
3
4
5
6
7
16
Building Technologies
Fire Safety & Security Products
Pos. 1 and 6 in the following description is only relevant if B3Q700 is used as replacement for
FC700A.
By ordering FC700A or B3Q700 (for FT700A) the Pos. 1 and 6 is already done by default.
Preparation
When used as 'FC' load program file:
B3Q700 -> CIY0076x
Remove (mount again later)
Set 'S5-2' to 'ON' to switch on the overflow
blocking of the event memory
Adjust if necessary
Ground fault monitoring -> see chapter 14
Set as described in document 007831, chapter
'Ground fault monitoring'
Re-solder if control terminal is used as 'FC', see
description in document 007831
Insert
Connect line to control unit as described in the
system documentation
Install and connect on 'ST2'
9
7
7
8
Mount control terminal after completing the preparation work -> see document
007827 and connect all cables according to the system documentation.
Default
Program file as 'FT'
B3Q700 -> CTY0076x
Mounted
All switches 'S5' to 'OFF'
Inserted for 110Ω impedance
(G51)
Removed (the other monitors)
On 'X31'... 'X34' (use as 'FT' +
supply from control unit)
To be ordered separately, or to be
created with Word template DOT
(document 007874)
Plug-in terminals delivered
If not enclosed, order separately
5
X30
R49/50
R31...34
ST2
S5
1
3
6
4
8
Y33/34
X33/34
X31/32
Y31/32
007828_b_en_--