K3I110 Lon I/O P.c.b; B3Q580 Floor Repeater Panel - Siemens FC700A Installation And Hardware Commissioning

Fire detection system
Hide thumbs Also See for FC700A:
Table of Contents

Advertisement

Control terminal and floor repeater panels
10.6

K3I110 LON I/O p.c.b.

Pos.
Module
1
Programming switch 'S3': LON-Bus address Set according to the system documentation
2
Jumper 'X30': Ground fault monitoring
'Inputs'
3
Resistor 'R1': line termination element
'LON-Bus'
4
Jumper 'X39': Relay test
5
Jumper 'X21': Activate test LEDs
'H1'....'H16'
10.7

B3Q580 Floor repeater panel

Pos.
Module
1
Programming switch 'S3': LON-Bus address According to the system documentation
2
Programming switch 'S4-1': Buzzer off
3
Resistor 'R1': line termination element
'LON-Bus'
4
Inscription strips
24
Building Technologies
Fire Safety & Security Products
Preparation
Set according to the system documentation, see
description in document 007831
Stub line: if K3I110 is not the last device, re-
move resistor 'R1', see description in document
007831
Set to 'left' for test -> enable all relays, see
description in document 007831
Set to 'left' for commissioning, see description in
document 007831
4
5
X39
X21
X30
S3
R1
Install and connect data bus and LON-Bus cable, supply cable as well as pe-
ripheral equipment
Preparation
Set 'S4-1' to 'ON' for commissioning
Stub line: if B3Q580 is not the last device,
remove resistor 'R1', see description in docu-
ment 007831
Inscribe and insert
S4
R1
3
Afterwards connect LON-Bus cable and supply cable, installation -> see docu-
ment 007831.
2
H1
1
H16
3
2
S3
1
4
Default
Set Address 0
To 'right' (not monitored)
Inserted 100Ω
Set to 'right' (all relays blocked)
Set to 'right' (service LEDs deacti-
vated)
Default
Set Address 0
Set to 'OFF'
Inserted 100Ω
No inscription
Created with Word template DOT
(document 007874)
007828_b_en_--
09.2008