Acoustic Noise; Balance - Danfoss VLT FCM Series Manual

Table of Contents

Advertisement

1. The load drives the motor (at constant output
frequency from the frequency converter), i.e.
the load generates energy.
2. During deceleration ("ramp-down") if the moment of
inertia is high, the load is low and the ramp-down
time is too short for the energy to be dissipated
as a loss in the VLT frequency converter, the
motor and the installation.
The control unit attempts to correct the ramp if possible.
The inverter turns off to protect the transistors
and the intermediate circuit capacitors when a
certain voltage level is reached.
Mains drop-out
During a mains drop-out, FCM 300 Series continues
until the intermediate circuit voltage drops below the
minimum stop level, which is typically 15% below
FCM 300 Series's lowest rated supply voltage.
The time before the inverter stops depends on the mains
voltage before the drop-out and on the motor load.
Static overload
When FCM 300 Series is overloaded (the current
limit in parameter 221 has been reached), the
controls will reduce the output frequency in an
attempt to reduce the load.
If the overload is excessive, a current may occur that
makes the FC motor cut out after approx. 1.5 sec.

Acoustic noise

Below are the typical values measured at a distance
of 1 m from the unit at full load:
2 pole
FCM 305
FCM 311
FCM 315
FCM 322
FCM 330
FCM 340
62 dB(A)
FCM 355
64 dB(A)
FCM 375

Balance

The FCM 300 is balanced to class R according to
ISO8821 (reduced balance). For critical applications
especially at high speed (>4000 RPM) special
balance (class S) might be required.
88
4 pole
54 dB(A)
58 dB(A)
59 dB(A)
58 dB(A)
61 dB(A)
63 dB(A)
60 dB(A)
61 dB(A)
®
VLT
FCM Series
MG.03.H3.02 - VLT is a registered Danfoss trademark

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT FCM Series and is the answer not in the manual?

Questions and answers

Table of Contents

Save PDF