46
en | Product Description
1.15.11
NZM 0002 A Notification Appliance Zone Module
This module is used to connect two monitored primary lines for activating notification
appliances. Currents of up to 3 A per output are possible in conjunction with the HPD 0000
Power Distributor.
Labeling
B OUT1 / A OUT1 / B IN1 / A IN1
B OUT2 / A OUT2 / B IN2 / A IN2
DC + / DC -
BAT + / BAT -
SYNC GND / SYNC OUT
SYNC GND / SYNC IN
Technical specifications
Operating and display elements 4 LEDs (2 x red, alarm/2 x yellow, fault)
Input voltage
Maximum current consumption
- Standby mode (both zones)
- In the event of an alarm (both
zones)
Maximum output voltage
Maximum output current for:
- supply by panel rail
- external power supply
Dimensions (H x W x D)
Weight
1.15.12
RMH 0002 A Relay Module High Voltage
The module has two change-over contact relays (type C) for monitored connection of external
elements with feedback, e.g. electromagnetic door holders, fans, smoke dampers.Each relay
has one NO (normally open) contact and one NC (normally closed) contact, and is protected
by a 6.3 A fuse. The maximum permissible contact load is 5 A at 120 V/230 V AC and 5 A at
30 V DC. The relay module can also be used as an extinguishing system interface in
accordance with VdS 2496.
F.01U.028.089 | 5.4 | 2009.08
Connector
NAC zone 1
NAC zone 2
External power supply via the HPD 0000 A Power
Distributor
24 V DC input, battery voltage
Output synchronization
Input synchronization
2 buttons (LED test)
20 V DC to 30 V DC / 5 V DC ± 5%
40 mA
65 mA
29.5 V DC
500 mA per NAC zone (in the event of an alarm)
3 A per NAC zone (in the event of an alarm)
Approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
Approx. 135 g (approx. 4.8 ounces)
Product Information
Modular Fire Panel
Bosch Sicherheitssysteme GmbH